- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- After SI initiation, must wait for 60 second timer to reset.
- Then the SI reset PB for each train must be actuated.
- This will block any automatic SI actuation signal but manual SI is not blocked.
- To remove auto SI block, the Rx trip breakers must be cycled to remove the P-4 seal-in signal.
- Any signal
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
- Any signal
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- 100 psig decreasing in a 50 second time constant
- 2/3 PTs on 1/4 loops
- Enabled only when Steamline Press SI signal blocked.
- 81% (P-14)
- 2/3 LTs on any S/G
- Rx Trip Bkrs Open 550 °F
- 2/4 loops
- Any signal
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
|