- Loaded: BO or SI with BO
- 0 secs
- Loaded: BO or SI with BO
- 2 secs
- Loaded: SI with BO only
- 5 secs
- Loaded: SI with BO only
- 10 secs
- Loaded: BO or SI with BO
- 15 secs
- Loaded: BO or SI with BO
- 20 secs
- Loaded: BO or SI with BO
- 20 secs
- Loaded: BO or SI with BO
- 30 secs
- Loaded: BO with fire pump start signal present
- 120 secs
- Loaded: Phase B with BO
- 180 secs
- Loaded: Phase B with BO *
- 220 secs *
- *Time delay ONLY if Phase B Isolation present.
- Loaded: Phase B with BO *
- 220 secs *
- *Time delay ONLY if Phase B Isolation present.
- < 80% (5520 volts) for 1.25 seconds on any SD Bd (DS)
- 1/2
- < 93.5 % (6451 volts) for 5 minutes (DV)
- 1/2
- Auto Start blocks manual “Normal Stop” shutdown
- < 20 psig
- Inhibited on Auto Start
- > 205 °F
- Inhibited on Auto Start
- > 1” H2O positive
- Inhibited on Auto Start
- > 600 amps
- Only inservice when D/G is paralleled to Normal or Alternate Supply
- Inhibited on Auto Start
|