- IR High Flux Rod Stop
- > 20%
- 1/2
- Block Auto and Manual Rod Withdrawal
- PR High Flux Rod Stop
- > 103%
- 1/4
- Block Auto and Manual Rod Withdrawal
- OT ΔT Rod Stop & Turbine Runback
- 3% below Trip Setpoint
- 2/4
- Block Auto and Manual Rod Withdrawal & Runback Turbine
- OP ΔT Rod Stop & Turbine Runback
- 1% below Trip Setpoint
- 2/4
- Block Auto and Manual Rod Withdrawal & Runback Turbine
- Auto Rod Stop
- PT-1-73 < 15%
- 1/1
- Block Auto Rod Withdrawal
- Load Rejection
- PT-1-72 senses a load decrease > 10% in a 2 minute time constant
- 1/1
- Arm Steam Dumps in the Tave Mode
- Condenser Available
- Condenser Press < 3.5 psia and CCWP Bkr Racked In & Closed
- 2/2 press & 1/3 Bkr
- Enable Steam Dumps
- Control Bank D Rod Stop
- 220 Steps
- 1/1
- Block Auto Rod Withdrawal
- AMSAC Interlock
- > 40% Rx Power Equivalent
- 2/2 PT's
- Arms ATWS mitigation system actuation circuit
|