- 10.7% (Normal Cntmt.)
- 15% (Adverse Cntmt.)
- 2/3 any S/G
- Any signal
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
- Associated Train
- < 80% for 1.25 seconds
- Starts 20 seconds after associated SD Bd energized
- < 8% S/G Level
- > 40% power (as seen by main turbine)
- For > 22 seconds
- 360 second time delay dropout for this interlock
- 10.7% (Normal Cntmt.)
- 15% (Adverse Cntmt.)
- 2/3 any S/G
- Any signal
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
- Either train on associated unit
- < 80% for 1.25 seconds
- Starts immediately on undervoltage signal
- < 8% S/G Level
- > 40% power (as seen by main turbine)
- For > 22 seconds
- 360 second time delay dropout for this interlock
- 4300 RPM (U-1)
- 4380 RPM (U-2)
- 2/2 TSs ≥148°F
- 2/2 TSs ≥148°F
- Variable (changes each time we come up in power)
- Check with Instrument Dept.
- < 220 psig
- 1A MFPT 28 second time delay
- 1B MFPT 20 second time delay
- 2A MFPT 28 second time delay
- 2B MFPT 20 second time delay
- Any 1 of 3 signals
- S/G Level Hi-Hi
- 81% (P-14)
- 2/3 LTs on any S/G
- Rx Trip (P-4) with Lo Tave
- Rx Trip Bkrs Open 550 °F
- 2/4 loops
- SIS
- Containment Press Hi
- 1.54 psid
- 2/3 PTs
- No Block/Permissive
- Pressurizer Press. Low
- 1870 psig
- 2/3 PTs
- Manual Below P-11
- Steamline Press Low
- 600 psig
- 2/3 PTs on 1/4 loops
- Manual Below P-11
- Manual
|